{"id":2952,"date":"2022-08-13T16:29:30","date_gmt":"2022-08-13T08:29:30","guid":{"rendered":"http:\/\/gewabin.wangluocloud.com\/?p=2952"},"modified":"2024-01-11T16:47:34","modified_gmt":"2024-01-11T08:47:34","slug":"precautions-for-installation-of-closed-circuit-cooling-towers","status":"publish","type":"post","link":"https:\/\/gewabintech.com\/pt\/knowledge\/precautions-for-installation-of-closed-circuit-cooling-towers\/","title":{"rendered":"Precau\u00e7\u00f5es para a instala\u00e7\u00e3o de torres de refrigera\u00e7\u00e3o de circuito fechado"},"content":{"rendered":"<p>O fluido (g\u00e1s) arrefecido na torre de arrefecimento fechada deve ser compat\u00edvel com a serpentina de arrefecimento; caso contr\u00e1rio, isso provocar\u00e1 a corros\u00e3o da serpentina. Por exemplo, o amon\u00edaco, utilizado como refrigerante, \u00e9 incompat\u00edvel com tubos de cobre, e a salmoura e a \u00e1gua alcalina s\u00e3o incompat\u00edveis com tubos de a\u00e7o ao carbono e tubos de cobre. As torres de refrigera\u00e7\u00e3o fechadas m\u00faltiplas (refrigera\u00e7\u00e3o por evapora\u00e7\u00e3o) permitem alterar o n\u00famero de torres em funcionamento; no caso das torres de refrigera\u00e7\u00e3o fechadas com v\u00e1rios ventiladores, \u00e9 poss\u00edvel alterar o n\u00famero de ventiladores; \u00e9 poss\u00edvel alterar a velocidade de funcionamento ou o controlo de convers\u00e3o de frequ\u00eancia dos ventiladores; e \u00e9 poss\u00edvel alterar a quantidade de \u00e1gua pulverizada.<\/p>\n\n\n\n<p>A massa de vapor de \u00e1gua contida em cada metro c\u00fabico de ar h\u00famido constitui a humidade. O vapor de \u00e1gua no ar h\u00famido ocupa tamb\u00e9m todo o volume desse ar. Assim, a humidade na resina corresponde \u00e0 densidade do vapor de \u00e1gua no ar h\u00famido. A humidade \u00e9 a quantidade de vapor de \u00e1gua por unidade de volume de ar h\u00famido. A uma determinada temperatura, a humidade do ar atinge um valor mais elevado e passa a ser designada por \u00abhumidade m\u00e1xima\u00bb. O tempo e o espa\u00e7o apenas permitem determinar a quantidade de vapor de \u00e1gua presente no ar h\u00famido a um n\u00edvel elevado, mas n\u00e3o conseguem explicar a monotonia, a humidade ou a higroscopicidade do ar h\u00famido. A humidade relativa reflete o grau em que o teor de vapor de \u00e1gua se aproxima da satura\u00e7\u00e3o, o que \u00e9 geralmente designado por satura\u00e7\u00e3o. Na condi\u00e7\u00e3o de temperatura constante da resina no projeto 0-1, quanto menor for o valor da humidade relativa, maior ser\u00e1 a monotonia e mais forte ser\u00e1 a higroscopicidade. Quanto maior for o valor da humidade relativa, maior ser\u00e1 a humidade e mais fraca ser\u00e1 a capacidade de absorver humidade. Ap\u00f3s um per\u00edodo de funcionamento da torre de arrefecimento fechada, a \u00e1gua cont\u00e9m i\u00f5es de c\u00e1lcio e magn\u00e9sio, bem como \u00e1cido carb\u00f3nico. O carbonato forma-se quando o calor \u00e9 transferido atrav\u00e9s de uma superf\u00edcie met\u00e1lica. O oxig\u00e9nio dissolvido na \u00e1gua de arrefecimento pode causar corros\u00e3o do metal, ferrugem, forma\u00e7\u00e3o de incrusta\u00e7\u00f5es e obstru\u00e7\u00e3o dos tubos, resultando numa diminui\u00e7\u00e3o da troca de calor e na avaria da torre de arrefecimento. \u00c9 mesmo necess\u00e1rio pulverizar \u00e1gua de arrefecimento no exterior da estrutura; a acumula\u00e7\u00e3o de impurezas, tais como incrusta\u00e7\u00f5es, consumir\u00e1 energia, aumentando assim os custos de funcionamento e, ao mesmo tempo, corroer\u00e1 a parede interna do sistema de controlo e reduzir\u00e1 a sua vida \u00fatil; o sistema de arrefecimento por circula\u00e7\u00e3o de \u00e1gua da torre de arrefecimento fechada \u00e9 prop\u00edcio \u00e0 entrada de poeira e detritos. Quando a \u00e1gua de arrefecimento circula no sistema de circula\u00e7\u00e3o, d\u00e1 origem a muitos microrganismos e dep\u00f3sitos, o que reduz significativamente o efeito de arrefecimento e afeta o funcionamento normal; as impurezas na \u00e1gua em circula\u00e7\u00e3o provocam o bloqueio do enchimento e afetam o desempenho do equipamento do sistema.<\/p>\n\n\n\n<p>www.gwbrefrigeration.com<\/p>\n\n\n\n<figure class=\"wp-block-image size-full\"><img loading=\"lazy\" width=\"750\" height=\"551\" src=\"http:\/\/gewabin.wangluocloud.com\/wp-content\/uploads\/2024\/01\/81d6e401fe34187835b8-1.jpg\"  class=\"wp-image-2953\" srcset=\"https:\/\/gewabintech.com\/wp-content\/uploads\/2024\/01\/81d6e401fe34187835b8-1.jpg 750w, https:\/\/gewabintech.com\/wp-content\/uploads\/2024\/01\/81d6e401fe34187835b8-1-600x441.jpg 600w\" sizes=\"(max-width: 750px) 100vw, 750px\" title=\"Precau\u00e7\u00f5es para a instala\u00e7\u00e3o de torres de refrigera\u00e7\u00e3o de circuito fechado [ilustra\u00e7\u00e3o]\" alt=\"Precautions For Installation Of Closed Circuit Cooling Towers\u63d2\u56fe\" \/><\/figure>","protected":false},"excerpt":{"rendered":"<p>The fluid (gas) cooled in the closed cooling tower must be compatible with the cooling coil, otherwise it will lead to corrosion of the coil. For example, the refrigerant ammonia is incompatible with copper pipes, and brine and alkaline water are incompatible with carbon steel pipes and copper pipes. Multiple closed cooling towers (evaporative cooling) can change the number of working towers; for multi-fan closed cooling towers, the number of fans can be changed; the working speed or frequency conversion control of the fans can be changed; the amount of spray water can be changed. The mass of water vapor contained in each cubic meter of moist air becomes humidity. Water vapor in moist air also fills the entire volume of moist air. So the humidity in the resin is the density of water vapour in moist air. Humidity is the amount of water vapor per unit volume of moist air. At a certain temperature, the humidity of the plump air reaches a higher value and becomes plump humidity. Time and space can only elucidate how much moist air pays attention to water vapour in the hi level, but cannot explain the monotony or wetness and hygroscopicity of moist air. Relative humidity reflects the degree to which the water vapor content is close to plumpness, which is generally called plumpness. Under the constant temperature condition of the resin in the 0-1 design, the smaller the relative humidity value, the more monotonous, and the stronger the hygroscopicity. The higher the relative humidity value, the higher the humidity and the weaker the ability to absorb moisture. Calcium, magnesium ions and carbonic acid exist in the water after the closed cooling tower has been in operation for a period of time. Carbonate occurs when heat is transferred across a metal surface. Dissolved oxygen in cooling water can cause metal corrosion, rust, scaling, and blockage of pipes, resulting in decreased heat exchange and cooling tower failure. It is even necessary to spray cooling water outside the shell; the accumulation of impurities such as scaling will consume power, then increase the working cost, and at the same time will corrode the inner wall of the control and shorten the life of the control; the water circulation cooling system of the closed cooling tower is easy to enter Dust and debris. When the cooling water circulates in the circulation system, it will breed many microorganisms and deposits, which will seriously reduce the cooling effect and affect the normal operation; the impurities in the circulating water will cause the packing to be blocked and affect the equipment performance of the system. www.gwbrefrigeration.com<\/p>","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":[],"categories":[13],"tags":[],"acf":[],"_links":{"self":[{"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/posts\/2952"}],"collection":[{"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/comments?post=2952"}],"version-history":[{"count":1,"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/posts\/2952\/revisions"}],"predecessor-version":[{"id":2954,"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/posts\/2952\/revisions\/2954"}],"wp:attachment":[{"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/media?parent=2952"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/categories?post=2952"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/gewabintech.com\/pt\/wp-json\/wp\/v2\/tags?post=2952"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}